Bartow Center

Florida Agency for Health Care Administration citation I0ZJ-K0374-20240729

Survey date 2024-07-29 - inspection

No Actual Harm, Potential Minimal (CLASS_III)
Corrected
Agency
Florida Agency for Health Care Administration
Citation code
I0ZJ-K0374-20240729
Severity
CLASS_III
Survey type
inspection
Source system
fl_ahca

What the regulator cited

SUBDIVISION OF BUILDING SPACES - SMOKE BARRIE Subdivision of Building Spaces - Smoke Barrier Doors 2012 EXISTING Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors. 19.3.7.6, 19.3.7.8, 19.3.7.9

What this severity rating means

No actual harm with a potential for minimal harm. The least severe class of CMS finding.

Resolution status

Corrected on 2024-08-30.